1) The distance from the transmitter surface of the sensor to the low liquid level should be less than the range of the optional instrument.
2) The distance from the transmitter surface of the sensor to the highest liquid level should be greater than the blind area of the optional instrument.
3) The transmitting surface of the sensor should be parallel to the liquid surface.
4) The installation position of the sensor should be as far as possible to avoid the position where the liquid level fluctuates sharply, such as the inlet and outlet below.
5) If the wall of the pool or tank is not smooth, the meter should be more than 0.3m away from the wall of the pool or tank.
6) If the distance from the transmitter surface of the sensor to the highest liquid level is less than the blind area of the optional instrument, it is necessary to install an extension tube, the extension tube diameter is greater than 120mm, the length is 0.35m ~ 0.50m, the vertical installation, the inner wall is smooth, the hole on the tank should be greater than the inner diameter of the extension tube. Or the pipe can be directly to the bottom of the tank, the diameter of the pipe is greater than 80mm, and the bottom of the pipe is left to facilitate the flow of liquid.